Calculator Hub

Science & Environment

Cooling Tower Evaporation & Blowdown Calculator

Estimate evaporation, drift and blowdown water losses in a cooling tower from circulation rate and cycles of concentration.

Your inputs

Change any value to update the result instantly.

Science & Environment
gpm
°F
%

Blowdown rate

2.83 gpm

Evaporation loss

8.5 gpm

Drift loss

0.2 gpm

Total makeup water

11.53 gpm

Formula and working

E = R × ΔT × 0.00085; D = E ÷ (COC − 1); Drift = R × driftRate

  1. 1

    Collect the inputs

    Circulation flow rate = 1,000 gpm; Range (ΔT) = 10 °F; Cycles of concentration = 4; Drift loss = 0.02 %

  2. 2

    Apply the formula

    E = R × ΔT × 0.00085; D = E ÷ (COC − 1); Drift = R × driftRate

  3. 3

    Result

    Blowdown rate = 2.83 gpm

Frequently asked questions

Important limitation

This is an educational estimate based only on the values and formula shown. Verify current rates, rules, units, and professional standards before relying on the result. It is not personalized financial or investment advice.

Report a mistake or request an improvement

Tell us if a formula, unit, explanation, or result needs attention. Your message will include this calculator’s name and page.